'''As remote''' – The remote Modbus register address or number that this local address should be viewed as by remote clients or masters. Follow the same rules for number, address, or Modicon register as for the local value.
 
'''As remote''' – The remote Modbus register address or number that this local address should be viewed as by remote clients or masters. Follow the same rules for number, address, or Modicon register as for the local value.
 
<hr>
 
<hr>
 
[[File:Modbus TCP server remap add header.jpg]]
 
  
 
[[File:Modbus server remap table empty.jpg]]
 
[[File:Modbus server remap table empty.jpg]]
 
<hr>
 
<hr>
 
Let's assume you start with the empty table above. You click the Add Maps button. The add/edit page is very simple.  
 
Let's assume you start with the empty table above. You click the Add Maps button. The add/edit page is very simple.  
[[File:Modbus server remap add.jpg]]
+
[[File:Modbus TCP server remap add header.jpg]][[File:Modbus server remap add.jpg]]
  
  
  
 
[[File:Modbus server remap table populated.jpg]]
 
[[File:Modbus server remap table populated.jpg]]

Revision as of 15:01, 2 May 2019

The edit page for server address map is very simple.

Modbus TCP server remap edit.jpg

Map local will indicate "number", "address", or "Modicon register", depending on your preference which you set under User Settings.

Register Number or Address – Enter the number (starting at 1) or raw address (starting at 0) as applicable. Do NOT enter 40001 for holding register 1 if you have not selected Modicon as the display format in your User Settings.

Modicon Register – Enter numbers like 40001 for the first holding register if you have selected Modicon representation in your User Settings.

As remote – The remote Modbus register address or number that this local address should be viewed as by remote clients or masters. Follow the same rules for number, address, or Modicon register as for the local value.


Modbus server remap table empty.jpg


Let's assume you start with the empty table above. You click the Add Maps button. The add/edit page is very simple. Modbus TCP server remap add header.jpgModbus server remap add.jpg


Modbus server remap table populated.jpg