Jimhogenson (talk | contribs) (Created page with "Note: The floating point branch (3) will default to OPAQUE DOUBLE (Net-SNMP type), but may be configured to be 32-bit or 64-bit Opaque Float or Double, or the 32-bit or 64-bit...") |
(No difference)
|
Latest revision as of 02:00, 10 April 2019
Note: The floating point branch (3) will default to OPAQUE DOUBLE (Net-SNMP type), but may be configured to be 32-bit or 64-bit Opaque Float or Double, or the 32-bit or 64-bit version of RFC 6340 Octet String interpretation. This selection is a configuration property of the SNMP agent task.
Index – Refers to the row number in the MIB table, ranging from 1 to maximum table size as set in the agent task configuration at startup.
Object – Refers to the local object number mapped at this location (branch and index) in the MIB.